HP (Hewlett-Packard) A9834-9001B Server User Manual


 
Chapter 2
System Specifications
Electrical Specifications
65
Figure 2-1 PDCA Locations
System Power Requirements
Table 2-8 and Table 2-9 list the ac power requirements for an HP Integrity Superdome/sx2000 system. These
tables provide information to help determine the amount of ac power needed for your computer room.
Table 2-8 Power Requirements (Without Support Management Station)
Requirement Value Comments
Nominal input voltage 200/208/220/230/
240 V ac rms
Input voltage range (minimum to maximum) 200 to 240 V ac
rms
Autoselecting (measured at
input terminals)
Frequency range (minimum to maximum) 50/60 Hz
Number of phases 3
Maximum in-rush current 90 A (peak)
PDCA 0
PDCA 1