HP (Hewlett-Packard) A9834-9001B Server User Manual


 
Chapter 3
Installing the System
Unpacking and Inspecting the System
89
Returning Equipment
If the equipment is found to be damaged, use the original packing material to repackage the cabinet for
shipment. If the packing material is not available, contact the local HP Sales and Support Office regarding
shipment.
Before shipping, place a tag on the container or equipment to identify the owner and the service to be
performed. Include the equipment model number and the full serial number, if applicable. The model number
and the full serial number are printed on the system information labels located at the bottom front of the
cabinet.
Table 3-1 Available Power Options
Option
Source
Type
Source Voltage
(Nominal)
PDCA
Required
Input Current
Per Phase 200
to 240 V ac
a
a. A dedicated branch circuit is required for each PDCA installed.
Power Receptacle
Required
6 3-phase Voltage range 200
to 240 V ac,
phase-to-phase,
50 Hz / 60 Hz
4-wire 44 A maximum
per phase
Connector and plug
provided with a 2.5 m (8.2
feet) power cable.
Electrician must hard wire
receptacle to 60 A site
power.
7 3-phase Voltage range 200
to 240 V ac,
phase-to-neutral,
50 Hz / 60 Hz
5-wire 24 A maximum
per phase
Connector and plug
provided with a 2.5 m (8.2
feet) power cable.
Electrician must hard wire
receptacle to 32 A site
power.
Table 3-2 Power Cord Option 6 and 7 Specifics
PDCA
Part Number
Attached Power Cord Attached Plug
Receptacle
Required
A5201-69023
(Option 6)
OLFLEX 190 (PN 600804) is a
2.5 meter multi conductor,
600 V, 90°C, UL and CSA
approved, oil resistant flexible
cable. (8 AWG 60 A capacity)
Mennekes
ME 460P9
(60 A capacity)
Mennekes
ME 460R9
(60 A capacity)
A5201-69024
(Option 7)
H07RN-F (OLFLEX PN
1600130) is a 2.5 meter
heavy-duty neoprene-jacketed
harmonized European flexible
cable. (4 mm
2
32 A capacity)
Mennekes
ME 532P6-14
(32 A capacity)
Mennekes
ME 532R6-1500
(32 A capacity)