HP (Hewlett-Packard) A9834-9001B Server User Manual


 
Chapter 2
System Specifications
Environmental Requirements
69
WARNING Do not connect a 380 to 415 V ac supply to a 4-wire PDCA. This is a safety hazard and
will result in damage to the product. Line-to-line or phase-to-phase voltage
measured at 380 to 415 V ac must always be connected using a 5-wire PDCA.
Table 2-15 Typical HP Integrity Superdome/sx2000 for Dual-core CPU
Configurations
a
a. Values in Table 2-15 are based on 25 W load I/O cards, 1
GB DIMMs and four Intel
Itanium 2 dual-core
processors with 18 MB or 24 MB cache per cell board.
Cell Memory IO
Typical
Power
(Watts)
Cooling
(Btu/Hr)
Breaker
Power
(Watts)
b
8 32 4 9490 32382 11957
8 16 2 7620 26001 9601
8 8 4 8140 27776 10256
8 8 2 7180 24500 9047
8 4 4 7620 26001 9601
8 4 2 6660 22726 8391
6 16 4 7320 24978 9223
6 16 2 6360 21702 8013
6 8 4 7000 23886 8820
6 8 2 6040 20610 7610
6 4 4 6680 22794 8417
6 4 2 5720 19518 7207
4 16 4 6170 21054 7774
4 16 2 5210 17778 6564
4 8 4 5960 20337 7509
4 8 2 5000 17061 6300
4 4 4 5760 19655 7257
4 4 2 4800 16379 6048
2 16 2 4010 13683 5052
2 8 2 3890 13274 4901
2 4 2 3780 12898 4763