Chapter 2
System Specifications
Environmental Requirements
70
b. These numbers are valid only for the specific
configurations shown. Any upgrades may require a
change to the breaker size. A 5-wire source utilizes a
4-pole breaker, and a 4-wire source utilizes a 3-pole
breaker. The protective earth (PE) ground wire is not
switched.
Table 2-16 Typical HP Integrity Superdome/sx2000 for Single-core CPU
Configurations
a
Cell Memory IO
Typical
Power
(Watts)
Cooling
(Btu/Hr)
Breaker
Power
(Watts)
b
8 32 4 9130 31181 11503
8 16 2 7260 24794 9147
8 8 4 7783 26580 9806
8 8 2 6823 23302 8596
8 4 4 7260 24794 9147
8 4 2 6300 21516 7938
6 16 4 6968 23797 8779
6 16 2 6008 20518 7570
6 8 4 6640 22677 8366
6 8 2 5680 19398 7156
6 4 4 6325 21601 7969
6 4 2 5365 18322 6759
4 16 4 5813 19852 7324
4 16 2 4853 16574 6114
4 8 4 4647 15870 5855
4 8 2 3687 12592 4645
4 4 4 5382 18380 6781
4 4 2 4422 15102 5571
2 16 2 3656 12486 4606
2 8 2 3534 12069 4453
2 4 2 3423 11690 4313
a. Values in Table 2-15 are based on 25 W load I/O cards, 1
GB DIMMs and four Intel
Itanium 2 single-core
processors with 9 MB cache per cell board.