Hitachi J300U Series Power Supply User Manual


 
12-11
Display
(Function mode 1) (Function mode 2)
Setting, change
sequence
Function Function Initialization display Initialization
contents
Setting contents
No. name contents
Frequency IN F-SAMP 8 8 1 to 8
command
sampling
frequency
setting
25 F-32 Arrival ARV PTN CST CST CST/PAT/ANY CST: Output at constant
Frequency
signal output
frequency arrival
arrival pattern PAT: Output of more than
output selection set frequency
signal ANY: Output of only set
frequency
Arrival ARV ACC 0.0 Hz 0 Hz 0 to 400.0
frequency
rate setting
for
acceleration
Arrival ARV DEC 0.0 Hz 0 Hz 0 to 400.0
frequency
rate setting
for
deceleration
26 F-33 Overtorque OV-TRQ V 100% 100% 0 to 250 • During control of SLV
Over- signal rate and V2: Power running
torque setting overtorque level
signal (for power • During control of VC
(NOTE 1) running) and VP1 to VP3:
Warning level for power
running regenerative
overload
• When 0 is set: Any signal
is not output.
Overtorque OV-TRQ R 100% 100% 0 to 250 During control of SLV
signal rate and V2: Regenerative
setting overtorque level
(for regen- • During control of VC
eration) and VP1 to VP3: No
effect
• When 0 is set: Any signal
is not output.
27 F-34 Input IN-TM 1 RS RS reset RS and 17
Intelligent terminal 1 terminal other terminals
terminal setting
input Input IN-TM 2 AT AT current AT and 17
terminal terminal 2
input selection
other terminals
setting setting terminal
Input IN-TM 3 JG JG jogging JG and17
terminal 3 terminal other terminals
setting
Input IN-TM 4 FRS FRS free FRS and 17
terminal 4 run other terminals
setting terminal
Input IN TM 5 CH1 CH1 2-stage CH1 and 17
terminal 5 acceleration other terminals
setting and
deceleration
terminal
NOTE 1: When setting 20% or less, the error will increase (± 20% or more).
Therefore, set 20% or more.