Hitachi J300U Series Power Supply User Manual


 
10-4
Daily Inspection and Periodic Inspection (2/3)
Inspection cycle
Inspection
location
Inspection item Inspection content Inspection method Criteria
Standard
replacement
period
Instruments
Main
circuit
Terminal board No damage. Visual inspection No abnormalities.
Smoothing
capacitor
(1) Check for leaking
(2) Check for swelling
Visual inspection of
(1) and (2).
No abnormalities in (1) and
(2).
5 years
(Note 1)
Relays (1) Check for stuttering noise
when operating
(1) Aural inspec-
tion.
(1) No abnormalities.
5 years
Regularly
Periodic
Resistors (1) Check for large cracks
or changes in color
(1) Visual inspection. (1) No abnormalities.
Cooling fan (1) Check for abnormal
vibrations and noise
(2) Check for dust
(1) Rotate manually
with power off
and increase
tightening
(2) Visual inspection
(1) Smooth rotation
(2) No abnormality
2 - 3 years