Hitachi J300U Series Power Supply User Manual


 
7-25
Contents and display
Extension
function
code
1
2
1
2
FUNC
FUNC
Base
frequency
setting
Maximum
frequency
setting
Set the base frequency and maximum frequency.
Setting method
Initial value
Setting example
V
100%
0
60 Hz
f
V
100%
0
60 Hz 120 Hz
f
When the frequency is set so that the base
frequency is larger than the maximum
frequency, the base frequency is forced
to be made equal to the maximum
frequency at the start of running.
Freely setting range
V
100%
(A62) base frequency
and (A63) maximum
frequency: 60 Hz
(A62) base frequency: 60 Hz
(A63) maximum frequency:
120 Hz
NOTE 1:
NOTE 2:
When a frequency more than the base frequency 60 Hz
is used, the motor is not a general purpose motor but
a special motor. Therefore, the maximum applicable
motor set value is different.
When the kW display is the same, the inverter
capacity may be increased.
Set the base frequency according to the specifications
of the motor. When the base frequency is set to less
than 50 Hz, the motor may be burned.
0
400 Hz
f
120 Hz60 Hz30 Hz
(400)
(NOTE 3)
Adjust the relationship between the external frequency command and the inverter output frequency.
Frequency
command
output
frequency
adjust
(O-L, OI-L)
: Voltage command (O-L)
: Current command (OI-L)
This function is factory-set to the appropriate position. If this setting is changed unnecessarily, the
correct relationship between the external frequency command and output frequency is no longer
maintained. This will result in poor control performance. Adjust the setting of this function only
when the output frequency does not conform to the external command.
Adjustment method
Voltage command:
Current command:
Put voltage command (10V of 5V) to O-L terminal, and adjust unit
output frequency comes to maximum.
Put current command (4-20mH) to OI-L terminal, and adjust unit
output frequency comes to maximum.
Maximum
frequency
selection
1
2
FUNC
Select 120 Hz or 400 Hz as the upper limit that can be set in the maximum frequency setting (A63).
Initial value