Hitachi J300U Series Power Supply User Manual


 
12-7
Display
(Function mode 1) (Function mode 2)
Setting, change
sequence
Function Function Initialization display Initialization
contents
Setting contents
No. name contents
9 F-08 Accelera- Fsp F 0000.0 Hz 0 Hz 0 to 400.0 • The frequency at which the
Accelera- tion stop acceleration operation is
tion halt frequency stopped temporarily is set.
setting
Accelera- Fsp TIME 00.0 s 0 s 0 to 60.0 The time that the acceleration
tion stop is stopped temporarily at a
time setting certain frequency during
acceleration is set.
10 F-09 Pattern PARAM REM REM REM/ • The parameter setting com-
command- OP1/OP2 manding source is selected.
ing method (Option REM (each operator),
selection connected) OP1 (option 1), OP2 (option
2)
11 F-10
Running
mode
Running RUN MODE NOR NOR NOR/OEN/ NOR: Normal running
mode GOD OEN: Energy conservation
selection running
GOD: Fuzzy most suitable
acceleration and
deceleration running
Restarting RUN FRS ZST ZST fST/ZST fST: Restart after frequency
after FRS maching
signal ZST: 0 Hz start
selection
12 F-11 Multistage SPD 1 0000.00 Hz 0 Hz 0 to 120.0 (400) The input terminal CF1 is set
Multistage speed and used.
speed 1 speed
setting
Multistage SPD 2 0000.00 Hz 0 Hz 0 to 120.0 (400) • The input terminal CF2 is set
speed and used.
2-speed
setting
Multistage SPD 3 0000.00 Hz 0 Hz 0 to 120.0 (400) The input terminals CF1 and
speed CF2 are set and used.
3-speed
setting
Multistage SPD 4 0000.00 Hz 0 Hz 0 to 120.0 (400) The input terminals CF1 and
speed CF3 are set and used.
4-speed
setting
Multistage SPD 5 0000.00 Hz 0 Hz 0 to 120.0 (400) The input terminals CF2 and
speed CF3 are set and used.
5-speed
setting
Multistage SPD 6 0000.00 Hz 0 Hz 0 to 120.0 (400) The input terminals CF1, CF2,
speed and CF3 are set and used.
6-speed
setting
Multistage SPD 7 0000.00 Hz 0 Hz 0 to 120.0 (400) • The input terminal CF3 is set
speed and used.
7-speed
setting