Hitachi J300U Series Power Supply User Manual


 
12-5
12.3 Function mode
Function mode list when the remote operator is used
Function mode initial values and display contents
Initial display contents, initialization, and change ranges are displayed in the table
indicated below.
Display
(Function mode 1) (Function mode 2)
Setting, change
sequence
Function Function Initialization display Initialization
contents
Setting contents
No. name contents
1 F-00 Base F-BASE 0060 Hz 60 Hz 30 to 120 (400) • When 120 Hz is switched to
frequency 400 Hz by F-30, a frequency
setting more than 120 Hz can be set.
2 F-01 Maximum F-MAX 0060 Hz 60 Hz 30 to 120 (400)
frequency
setting
3 F-02 Start Fmin 0.50 Hz 0.5 Hz 0.1 to 9.9 • The equipment starts running
frequency at this set value.
adjustment
4 F-03 Motor input AVR AC 460 V 230/460 200,215,220,230 • The motor input voltage is set.
Input voltage /380,400,415
voltage setting 440,460,480
AVR AVRDEC OFF OFF ON/OFF • ON or OFF of the AVR
function function for deceleration
for is set. When dynamic
decelera- braking torque is necessary
tion for deceleration, OFF is set.
5 F-04 Control CONTROL VC VC VC, VP1, VP2, • VC, VP1, VP2, VP3:
method VP3, SLV, V2 V/F characteristics
setting SLV:Sensorless vector control
V2:Sensor vector control
6 F-05 Autotuning AUX AUTO NOR NOR NOR/AUT/NRT • At the first running after
Motor setting AUT/NRT is set, the
constant autotuning measurement
(NOTE 1) operation is executed.
Motor data AUX DATA NOR NOR NOR: Old Hitachi The autotuning motor data
selection general purpose before starting autotuning
TMO: New measurement is data
Hitachi general equivalent to NOR.
purpose
AUT: Auto-
tuning data
Motor AUX K 005.50 kW
Rated capacity
3.7 to 160 Set a capacity smaller than the
capacity
of each inverter
rated capacity as capacity
setting data.
Motor pole AUX P 4p 4p 2, 4, 6, 8 The number of poles of the
count motor to be used is set.
setting
Motor AUX R1 1.004
Rated capacity
0 to 65.535
constant
of each inverter
R1 setting
Motor AUX R2 0.776
Rated capacity
0 to 65.535
constant
of each inverter
R2 setting
Motor AUX L 13.16 mH
Rated capacity
0 to 655.35
constant
of each inverter
L setting
NOTE 1: The motor constants R1, R2, L, M, J, Kp, Ti, and KPP vary with the capacity.