Xantrex Technology XMP 2600 Power Supply User Manual


 
Installation Rear Panel Description
option 2
Vin=0V modules operation inhibited
Vin=4VDC to 12VDC modules operation enabled
Connect as follows:
+Vin @ pin 3
-Vin @ pin 11
Short pins #5 and #13.
the +Vin and -Vin terminals are isolated and can be floated up to
±200VDC relative to the earth potential.
option 3
+/-SHORT shorted modules operation enabled
+/-SHORT open modules operation inhibited
Connect as follows:
+SHORT @ pin 2
-SHORT @ pin 11
Short pins #1 and #9.
Short pins #4 and #12.
the -SHORT pin is the GND of the RS-232 and the IEEE-488.
option 4
+/-SHORT shorted modules operation inhibited
+/-SHORT open modules operation enabled
Connect as follows:
+SHORT @ pin 2
-SHORT @ pin 11
Short pins #1 and #9.
Short pins #4 and #12.
Short pins #5 and #13.
the -SHORT pin is the GND of the RS-232 and the IEEE-488.
The dry contact outputs are as follow:
Pin #7 shorted to pin #6 when the modules are operating.
Pin #7 shorted to pin #14 when the modules are not operating.
These output indications are floating, isolated to 200VDC from earth ground.
XMP 2600 User’s Guide
rev. 1.0 9