Parameters Functions Settings
Factory
Setting
Customer
37: PLC program operation
Paused
03-08 Master Frequency Attained 1 0.00~120.00 Hz 0.00
03-09 Master Frequency Attained 2 0.00~120.00 Hz 0.00
03-10 Analog Output 1, (AFM1)
0~10Vdc
00
03-11 Analog Output 2, (AFM2)
0/4~ 20mA
00: Output frequency
01: Output current
02: Output voltage
03: Frequency command
04: Power factor loading
01
a
03-12 Analog Output Gain 1 01~200%
100
a
03-13 Analog Output Gain 2 01~200%
100
03-14 Analog Output 2 Selection
(AFM2 Definition)
00: 0~20mA
01: 4~20mA
01
03-15 DC Fan Control 00: Fan runs on power up.
01: Fan begins upon a RUN
command. Fan stops 1
minute after a STOP
command.
02: Fan begins upon a RUN
command. Fan stops
after a STOP command
03: Fan is controlled by
temperature.
Approximately a 60°C
temperature will start the
fan.
00