Delta Electronics VFD-F Series Network Card User Manual


 
5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-33
1
2
3
4
5
60Hz or more
50Hz
10Hz
5Hz
Load
factor
(%)
Operation
Time(min)
0
20
40
60
80
100
120
140
160
180 200
06 - 08 Low Current Detection Level
Factory Setting: 00
Settings 00~100% (00 disabled) Unit: 1
06 - 09 Low Current Detection Time
Factory Setting: 10.0
Settings 0.1~ 3600.0 Sec Unit: 0.1
06 - 10 Low Current Detection Treatment
Factory Setting: 01
Settings
00: Warn and Ramp to stop
01: Warn and Coast to stop
02: Warn and keep operating
These parameters set the low current detection mode, time, and operation.
06 - 11 Present Fault Record
Factory Setting: 00
06 - 12 Second Most Recent Fault Record
Factory Setting: 00
06 - 13 Third Most Recent Fault Record
Factory Setting: 00
06 - 14 Fourth Recent Fault Record
Factory Setting: 00
Settings 00 No fault occurred
01 Over-current (oc)
02 Over-voltage (ov)
03 Overheat (oH)
04 Overload (oL)
05 Electronic thermal relay (oL1)
06 External fault (EF)
07 AC drive IGBT fault (occ)
08 CPU failure (cF3)
09 Hardware protection failure (HPF)