08 - 10 Auto Restart Time after Fault
Factory Setting: 600
Settings 00 to 60000 sec Unit:
This parameter determines auto restart time after fault. After fault occurs and restart, there
is no fault occurs during 08-10 setting time, AC drive will reset fault occurred record to zero.
08 - 11
Operation Frequency Inhibition 1 UP Factory Setting: 0.00
08 - 12
Operation Frequency Inhibition
1 DOWN Factory Setting: 0.00
08 - 13
Operation Frequency Inhibition 2 UP Factory Setting: 0.00
08 - 14
Operation Frequency Inhibition
2 DOWN Factory Setting: 0.00
08 - 15
Operation Frequency Inhibition 3 UP Factory Setting: 0.00
08 - 16
Operation Frequency Inhibition
3 DOWN Factory Setting: 0.00
Settings 0.00~120.00 Hz Unit: 0.01
This parameter determines the inhibition operation frequency range. This function will let
AC drive not run continuous in the resonance frequency of the motor or loading system, or
inhibition operation frequency.
The settings of this parameter should follow as 08-1108-1208-1308-1408-15
08-16.
Master frequency command can be set in inhibition operation frequency range. Now the
output frequency will be limited in the lower bound of inhibition operation frequency.
When AC drive accelerates or decelerates, output frequency will pass through inhibition
operation frequency range.
08 - 17 Automatic Energy-saving
Factory Setting: 00
Settings
00: Energy-saving operation disabled
01: Energy-saving operation enabled
This parameter determines automatic energy-saving function.
70%
Output voltage
100%
Frequency
Automatic Energy-saving Operation
During the auto energy-saving
operation, it will adjust the output
voltage according to the output
power. The maximum output
voltage can be 30% lower than
the normal output voltage.