Delta Electronics VFD-F Series Network Card User Manual


 
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-36
5.8 Group 7: AC Drive and Motor Parameters
07 - 00 Identity Code of AC Drive
Factory Setting: ##
Settings Display by model type
This parameter displays the AC drive model code.
This parameter is read-only.
07 - 01 Rated Current of AC Drive
Factory Setting: ##
Settings Display by model type
This parameter displays rated output current of the AC drive. The following chart may be
used to look up the identity code, current, and hp of your drive.
230V series
KW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37
HP 1 2 3 5 7.5 10 15 20 25 30 40 50
Pr.07-00 4 6 8 10 12 14 16 18 20 22 24 26
Rated current (A) 5 7 11 17 25 33 49 65 75 90 120 145
Max. Carried Freq. 10KHz 9KHz 6KHz
Min. Carried Freq. 4KHz 3KHz 2KHz
Factory Setting 9KHz 6KHz 4KHz
460V series
KW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 130 160 185 220
HP 1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50 60 75 100 125 150 175 215 250 300
Pr.07-00 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45
Rated Current (A)
2.7
4.2 5.5 8.5 13 18 24 32 38 45 60 73 91 110 150 180 220 260 310 370 460
Max. Carried Freq. 10KHz 9KHz 6KHz
Min. Carried Freq. 4KHz 3KHz 2KHz
Factory Setting 9KHz 6KHz 4KHz
This parameter is read-only.
07 - 02 Full-load Current of Motor
a
Factory Setting: 100%
Settings 30~120% Unit: 1
This parameter selects the full load current of the motor.
Pr7-02 = (full load motor current / drive rated current)
Example: If the rated current of AC drive is 150A, full-load current of motor is 120A, then
Pr.7-02 should be set to 80%.