Delta Electronics VFD-F Series Network Card User Manual


 
5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-17
External relay specifications = 8A/250VAC or 5A/30VDC.
Relay delay time is 5~10 msec.
03 - 08 Master Frequency Attained 1
Factory Setting: 0.00
03 - 09 Master Frequency Attained 2
Settings 0.00~120.00 Hz Unit: 0.01
An output relay may be programmed to activate when the output frequency exceeds the
desired attained frequency setting of these two parameters.
There is a
±
2Hz window of operation. If the master frequency attained is 20Hz and the
output frequency exceeds 20Hz, the corresponding output relay will be “closed”. When the
output frequency is less than 18Hz, the corresponding output relay will be “opened” as the
following diagram shows.
Frequency
Master
frequency 1
Master frequency
2 attained
Master frequency
attained
Output frequency
Frequency
command
Time
2Hz
4Hz
2Hz
2Hz
Master frequency
1 attained
Master
frequency 2
03 - 10 Analog Output 1, (AFM1) 0~10Vdc
Factory Setting: 00
03 - 11 Analog Output 2, (AFM2) 0/4~ 20mA
Factory Setting: 01
Settings
00: Output frequency
01: Output current
02: Output voltage
03: Frequency command
04: Power factor loading
These parameters select the content of the analog output signals AFM1 and AFM2.
Setting 00: 0-10V = 0 - (Pr.01-00)
Setting 01: 0-10V = 0 - (2.52.0 x rated current)
Setting 02: 0-10V = 0 - (Pr.01-02)
Setting 03: 0-10V = 0 - Master Freq. command