Group 11 Fan and Pump Control Parameters
Parameters Functions Settings
Factory
Setting
Customer
11-00 V/F Curve Selection 00: Determined by group 01
01: 1.5 power curve
02: 1.7 power curve
03: 2 power curve
04: 3 power curve
00
11-01 Circulative Control 00: No function
01: Time circulation (by time)
02: Fixed amount circulation
(by PID)
03: Fixed amount control (an
AC drive runs with 4
motors)
00
11-02 Multiple Motors Control 01~04 01
11-03 Time Circulation Time Setting 00~65500 Min 00
11-04 Motor Switch Delay Time 0.0~3600.0 sec 1.0
11-05 Motor Switch Delay Time during
Fixed Amount Circulation
0.0~3600.0 sec 10.0
11-06 Motor Switch Frequency during
Fixed Amount Circulation
0.00 to 120.00 Hz 60.00
11-07 Enter Sleep Process Time 0.0~3600.0sec
0.0: Sleep function disable
0.0
11-08 Sleep Frequency of Sleep
Process
0.00 to 11-09
(Wake up Frequency)
0.0
11-09 Wake Up Frequency of Sleep
Process
0.00 to 120.0Hz 0.0
11-10 Treatment of Fixed Amount
Circulation Malfunction
00: Turn off all motors
01: Turn off AC drive
00
11-11 Stop Frequency of Auxiliary
Motor
0.00~120.00Hz 0.00