Delta Electronics VFD-F Series Network Card User Manual


 
4
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
4-5
4.2 KPF-CC01
For models of VFD-F (HVAC) series
VFD007F43H; VFD015F43H; VFD022F43H; VFD037F43H; VFD055F43H; VFD075F43H;
VFD110F43H; VFD150F43H; VFD185F43H; VFD220F43H; VFD300F43H; VFD370F43H;
VFD450F43H; VFD550F43H; VFD750F43H; VFD900F43H; VFD1100F43H; VFD1320F43H;
VFD1600F43H; VFD1850F43H; VFD2200F43H
NOTE
When KPF-CC01 is connected on AC motor drive, the communication protocol is forced to be 9600, 8,
N, 2. After KPF-CC01 is disconnected, and AC motor drive immediately gets connection with other
controller by RS-485, 1st communication fault may occur due to different communication protocol. AC
motor drive will automatically reset communication protocol as previous parameter setting from 2nd
communication.
4.2.1 Description of the Digital Keypad KPF-CC01
LCD Display
Indicates frequency, voltage, current, user
defined units, read, and save etc.
Model Number
Status Display
Display the driver current status.'s
MODE
Change between different display mode.
Parameter Unit key
Switch the operation command source.
Right key
Moves the cursor right.
PROG/DATA
Used to enter programming parameters.
STOP/RESET
Stops AC drive operation or reset the drive
after fault occurred.
JOG Operation key
Press this key to execute
the JOG frequency operation.
Left key
Moves the cursor left.
UP and DOWN key
Set the parameter number and
changes the numerical data, such
as Master Frequency.
FWD/REV Direction key
Select FWD/REV operation
RUN key
Start AC drive operation.
4.2.2 Explanation of Display Message
Display Message Description
The AC motor drive Master Frequency Command.
The Actual Operation Frequency present at terminals U, V, W.