Delta Electronics VFD-F Series Network Card User Manual


 
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
B-10
B.3 AC Reactor
AC Input Reactor Recommended Value
460V, 50/60Hz, 3-Phase
Inductance (mh)
KW HP
Fundamental
Amps
Max. Continuous
Amps
3% impedance 5% impedance
0.75
1 4 6 9 12
1.5
2 4 6 6.5 9
2.2
3 8 12 5 7.5
3.7
5 8 12 3 5
5.5
7.5 12 18 2.5 4.2
7.5
10 18 27 1.5 2.5
11
15 25 37.5 1.2 2
15
20 35 52.5 0.8 1.2
18.5
25 35 52.5 0.8 1.2
22
30 45 67.5 0.7 1.2
30
40 55 82.5 0.5 0.85
37
50 80 120 0.4 0.7
45
60 80 120 0.4 0.7
55
75 100 150 0.3 0.45
75
100 130 195 0.2 0.3
90
125 160 240 0.15 0.23
110
150 200 300 0.11 0.185
132
175 250 375 0.09 0.15
160
215 320 480 0.075 0.125
185
250 400 560 0.06 0.105
220
300 500 700 0.05 0.085
460V DC Choke
Input Voltage
kW
HP DC Amps Inductance (mh)
0.75
1 4 25.00
1.5
2 9 11.50
2.2
3 9 11.50
3.7
5 12 6.00
5.5
7.5 18 3.75
7.5
10 25 4.00
11
15 32 2.68
15
20 50 2.00
NOTE
18.5kW~132kW models: built-in DC choke
160kW~220kW models: built-in AC reactor