Parameter
Menu Navigation
Date
Main Menu / Settings / Controller / Date
Time
Main Menu / Settings / Controller / Time
Float Voltage
Main Menu / Settings / Battery / Charge / Float Voltage
Equalize Voltage
Main Menu / Settings / Battery / Charge / EQ Voltage
Temperature Compensation
Center Temperature
Main Menu / Settings / Battery / Temp Comp / Temp CompCenter
Temperature Compensation
Slope
Main Menu / Settings / Battery / Temp Comp / Temp Comp Coeff
Temperature Compensation
Sensor
Main Menu / Settings / Battery / Temp Comp / TempComp Sensor
Temperature Compensation
Maximum Voltage
Main Menu / Settings / Battery / Temp Comp / Temp Comp Max V
Temperature Compensation
Minimum Voltage
Main Menu / Settings / Battery / Temp Comp / Temp Comp Min V
HVSD Limit
Main Menu / Settings / Rectifier / All Rect Set / HVSD Limit
Rectifier Current Limit
Main Menu / Settings / Rectifier / All Rect Set / Curr Limit Pt
Over Voltage Alarm 1
Main Menu / Settings / Power System / General / 24V Over Volt1
Over Voltage Alarm 2
Main Menu / Settings / Power System / General / 24V Over Volt2
Under Voltage Alarm 1
Main Menu / Settings / Power System / General / 24V Under Volt1
Under Voltage Alarm 2
Main Menu / Settings / Power System / General / 24V Under Volt2