Emerson 710NPBA Power Supply User Manual


 
IM581127000 Installation Instructions
Issue AB, March 22, 2012 Spec. No. 581127000 (Model 710NPBA)
Page 84 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-16
Battery Landing Busbar Kit P/N 550265
(Two Row Cabinet
Shown, Others Similar)
Rear View
Plastic Shield
1. Remove top Rear Access Cover
from distribution cabinet
(note that the complete
rear cover is removed in the
illustration for clarity only).
2. Attach Return Angle Bracket.
3. Attach +24V Angle Bracket.
4. Secure rear cover shield
to distribution cabinet
after wiring.
Return Angle Bracket
Secure 2 places
with (in order listed)
3/8-16 x 1-1/4Bolt,
3/8Belleville Lockwasher,
and 3/8Flat Washer.
Torque to 180 in-lbs.
+24V Angle Bracket
Secure in 2 places
with existing hardware
(in order listed)
1/2-13 x 1-1/4Bolt,
1/2Belleville Lockwasher,
1/2Flat Washer.
Torque to 200 in-lbs.
Apply electrical anti-oxidizing
compound to busbar mating surfaces.
Hardware attached
from other side.