Emerson 710NPBA Power Supply User Manual


 
Installation Instructions IM581127000
Spec. No. 581127000 (Model 710NPBA) Issue AB, March 22, 2012
Chapter 3. Setting Jumpers and Switch Options Page 35
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
DIP Switch SW1
Reserved
HW/
SW
Shunt
Voltage
Shunt
Current
Description
of Status
1
2
3
4
5
6
7
8
NA
OFF
NA
Shunt parameter is set through DIP switch.
ON
Shunt parameter is set through software (note 1).
NA
OFF
OFF
NA
Shunt Voltage: 25mV (note 1)
OFF
ON
Shunt Voltage: 50mV
ON
OFF
Shunt Voltage: 60mV
ON
ON
Shunt Voltage: 75mV
NA
OFF
OFF
OFF
Shunt Current: 500A (note 1)
OFF
OFF
ON
Shunt Current: 100A
OFF
ON
OFF
Shunt Current: 200A
OFF
ON
ON
Shunt Current: 300A
ON
OFF
OFF
Shunt Current: 400A
ON
OFF
ON
Shunt Current: 1000A
ON
ON
OFF
Shunt Current: 1500A
ON
ON
ON
Shunt Current: 2000A
DIP Switch SW2
Reserved
Communications
Address
Baud
Rate
Description
of Status
1
2
3
4
5
6
7
8
NA
OFF
OFF
OFF
NA
Address 1# (Setting for SM-DU+ in this system)
OFF
OFF
ON
Address 2#
OFF
ON
OFF
Address 3#
OFF
ON
ON
Address 4#
ON
OFF
OFF
Address 5#
ON
OFF
ON
Address 6#
ON
ON
OFF
Address 7#
ON
ON
ON
Address 8#
NA
OFF
19200 (note 1)
ON
9600
Note 1: Setting for this system.
Table 3-3
Optional SM-DU+ Board DIP Switch Settings