Emerson 710NPBA Power Supply User Manual


 
Installation Instructions IM581127000
Spec. No. 581127000 (Model 710NPBA) Issue AB, March 22, 2012
Chapter 4. Making Electrical Connections Page 73
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Load Connections to Return Bar
List GA: Return Bar Panel
Load Connections to GMT Distribution Fuse Block
Optional Bullet Nose 6-Position GMT Distribution Fuse Block
Load and/or Battery
Return Connections
LOAD AND/OR BATTERY RETURN CONNECTIONS
3/8-16 Captive Nuts on 1Centers
(Customer must supply or order additional hardware)
Maximum Lug Width: 1.38 inches.
Load Return Leads
+24VDC Load Leads
Wire Size Capacity: 26-14 AWG.
Recommended Torque: 4.5 in-lbs.
35A maximum capacity per block.
Maximum GMT fuse size is 15A.