6) Adjust the “IB2 Temp1 High 2setpoint to 10 degrees below the temperature
recorded in step 2).
a) Requirement: An “IB2 Temp1 High 2” alarm is displayed.
b) Requirement: External “Relay 12 High 2 Battery Temperature Alarm
(requires EIB Interface Board to be installed in the system) activates.
7) Using the Web Interface, adjust the “IB2 Temp1 High 2” setting to the value
recorded in step 5).
8) Using the Web Interface, adjust the “IB2 Temp1 High 1” setting to the value
recorded in step 3).
a) Requirement: No alarms are displayed on the Web Interface screen.
b) Requirement: The external alarm deactivates.