Page 20 Chapter 2. Installing the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 2-11
Installing an Optional Bullet Nose Type 6-Position GMT Distribution Fuse Block
Press in tabs to release
lug terminal busbars for
positions to be occupied
by GMT Fuse Block.
Remove two lug terminal busbars
for positions to be occupied
by GMT Fuse Block.
Plug in GMT Fuse Block and secure
at two locations on the RTN bar.
Torque to 72 in-lbs.
RTN Bar
GMT Fuse Block Installed View