Installation Instructions IM581127000
Spec. No. 581127000 (Model 710NPBA) Issue AB, March 22, 2012
Chapter 2. Installing the System Page 25
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 2-14 (cont’d from previous page)
Installing a GJ/218 Circuit Breaker (2-Pole, 3-Pole, 4-Pole)
1/4" Hardened
Flat Washer
1/4" Belleville
Lock Washer
1/4-20 x 3/4” Bolt
(4 places)
Torque to 60 in-lbs.
Apply anti-oxidizing compound to busbar mating
surfaces before mounting circuit breakers.
OFF
ON
INSTALLING CIRCUIT BREAKER GUARD
INSTALLING CIRCUIT BREAKER
Alarm jumper connectors.
Holes to route shunt jumper through (if applicable).
ALARM WIRING (BREAKERS W/OUT SHUNTS)
ALARM WIRING (BREAKERS WITH SHUNTS)
Busbar
2-pole breaker shown.
3-pole and 4-pole breakers similar.