Hitachi SJ700-2 Power Supply User Manual


 
Chapter 4 Explanation of Functions
Intelligent output terminals When "4 bits" is selected When "3 bits" is selected
14 13 12 11
AC3 AC2 AC1 AC0
Factor code Cause of tripping Factor code Cause of tripping
1 1 0 1 E20, E21
Temperature error due to
low cooling-fan speed
Temperature error
1 1 1 0 E24 Phase loss input protection
1 1 1 1 E50 to E79
Easy sequence user trip 0-9,
option 1,2 error 0-9
Item Function code Data Description
00 No output of alarm code
01 Output of 3-bit code
Alarm code output C062
02 Output of 4-bit code
4.2.66 Logical output signal operation function (LOG1 to LOG6)
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C142: Logical output signal 1 selection 1
C143: Logical output signal 1 selection 2
C144: Logical output signal 1 operator selection
C145: Logical output signal 2 selection 1
C146: Logical output signal 2 selection 2
C147: Logical output signal 2 operator selection
C148: Logical output signal 3 selection 1
C149: Logical output signal 3 selection 2
C150: Logical output signal 3 operator selection
C151: Logical output signal 4 selection 1
C152: Logical output signal 4 selection 2
C153: Logical output signal 4 operator selection
C154: Logical output signal 5 selection 1
C155: Logical output signal 5 selection 2
C156: Logical output signal 5 operator selection
C157: Logical output signal 6 selection 1
C158: Logical output signal 6 selection 2
C159: Logical output signal 6 operator selection
Related code
The logical output signal operation function allows you to make
the inverter internally perform a logical operation of output
signals.
This function applies to all output signals, except to logical
operation results (LOG1 to LOG6).
Three types of operators (AND, OR, and XOR) are selectable.
LOGx (AND)
LOGx (OR)
LOGx (XOR)
Output signal 1
Output signal 2
The necessary parameters depend on the logical output signal to be operated. The following table lists the
parameters to be set for each logical output signal:
Selected signal
Operation-target 1
selection
Operation-target 2
selection
Operator
selection
33: Logical output signal 1 (LOG1) C142 C143 C144
34: Logical output signal 2 (LOG2) C145 C146 C147
35: Logical output signal 3 (LOG3) C148 C149 C150
36: Logical output signal 4 (LOG4) C151 C152 C153
37: Logical output signal 5 (LOG5) C154 C155 C156
38: Logical output signal 6 (LOG6) C157 C158 C159
(Example) To output the AND of the running signal (00: RUN) and set the frequency overreached signal
(02: FA2) as the logical output signal 1 (LOG1) to the intelligent output terminal [2]:
- Intelligent output terminal [2] (C002): 33 (LOG1)
- Logical output signal 1 selection 1 (C142): 00 (RUN)
- Logical output signal 1 selection 2 (C143): 02 (FA2)
- Logical output signal 1 operator (C143): 00 (AND)
4 - 66