Hitachi SJ700-2 Power Supply User Manual


 
Chapter 8 List of Data Settings
8 - 3
8.4 Extended Function Mode
Default
Code Function name Monitored data or setting
_FF
_
FEF
_
FUF
Setting
during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
A001
Frequency source setting 00 (keypad potentiometer) (*1), 01 (control circuit terminal block), 02 (digital
operator), 03 (RS485), 04 (option 1), 05 (option 2), 06 (pulse-string input), 07
(easy sequence), 10 (operation function result)
02 01 01
¯ ¯
4-8
A002
Run command source setting 01 (control circuit terminal block), 02 (digital operator), 03 (RS485), 04 (option
1), 05 (option 2)
02 01 01
¯ ¯
4-8
A003 Base frequency setting 30. to "maximum frequency " (Hz) 60. 50. 60.
¯ ¯
A203
Base frequency setting, 2nd
motor
30. to "maximum frequency, 2nd motor" (Hz)
60. 50. 60.
¯ ¯
A303
Base frequency setting, 3rd
motor
30. to "maximum frequency, 3rd motor" (Hz)
60. 50. 60.
¯ ¯
4-11
A004 Maximum frequency setting 30. to 400. (Hz) 60. 50. 60.
¯ ¯
A204
Maximum frequency setting, 2nd
motor
30. to 400. (Hz)
60. 50. 60.
¯ ¯
Basic settings
A304
Maximum frequency setting, 3rd
motor
30. to 400. (Hz)
60. 50. 60.
¯ ¯
4-11
A005
[AT] selection 00 (switching between O and OI terminals), 01 (switching between O and O2
terminals), 02 (switching between O terminal and keypad potentiometer) (*1),
03 (switching between OI terminal and keypad potentiometer) (*1), 04
(switching between O2 and keypad potentiometer) (*1)
00
¯ ¯
A006
[O2] selection 00 (single), 01 (auxiliary frequency input via O and OI terminals)
(nonreversible), 02 (auxiliary frequency input via O and OI terminals)
(reversible), 03 (disabling O2 terminal)
03
¯ ¯
4-12
A011
[O]-[L] input active range start
frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯ {
A012
[O]-[L] input active range end
frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯ {
A013
[O]-[L] input active range start
voltage
0. to "[O]-[L] input active range end voltage" (%)
0.
¯ {
A014
[O]-[L] input active range end
voltage
"[O]-[L] input active range start voltage" to 100. (%)
100.
¯ {
A015
[O]-[L] input active range start
frequency selection
00 (external start frequency), 01 (0 Hz)
01
¯ {
4-14
A016
External frequency filter time
const.
1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)
31.
¯ {
4-15
Analog input and others
A017
Easy sequence function
selection
00 (disabling), 01 (enabling)
00
¯ ¯
4-95
A019
Multispeed operation selection 00 (binary: 16 speeds selectable with 4 terminals), 01 (bit: 8 speeds selectable
with 7 terminals)
00
¯ ¯
A020 Multispeed frequency setting 0.0 or “start frequency” to “maximum frequency” (Hz) 0.00
{ {
A220
Multispeed frequency setting,
2nd motor
0.0 or “start frequency” to “maximum frequency, 2nd motor” (Hz)
0.00
{ {
A320
Multispeed frequency setting,
3rd motor
0.0 or “start frequency” to “maximum frequency, 3rd motor” (Hz)
0.00
{ {
A021 Multispeed 1 setting 0.0 or “start frequency” to “1st maximum frequency” (Hz) 0.00
{ {
A022 Multispeed 2 setting 0.0 or “start frequency” to “2nd maximum frequency” (Hz) 0.00
{ {
A023 Multispeed 3 setting 0.0 or “start frequency” to “3rd maximum frequency” (Hz) 0.00
{ {
A024 Multispeed 4 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A025 Multispeed 5 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A026 Multispeed 6 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A027 Multispeed 7 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A028 Multispeed 8 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A029 Multispeed 9 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A030 Multispeed 10 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A031 Multispeed 11 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A032 Multispeed 12 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A033 Multispeed 13 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A034 Multispeed 14 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
A035 Multispeed 15 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
{ {
4-47
A038 Jog frequency setting "Start frequency" to 9.99 (Hz) 1.00
{ {
Multispeed operation and jogging
A039 Jog stop mode
00 (free-running after jogging stops [disabled during operation]), 01
(deceleration and stop after jogging stops [disabled during operation]), 02 (DC
braking after jogging stops [disabled during operation]), 03 (free-running after
jogging stops [enabled during operation]), 04 (deceleration and stop after
jogging stops [enabled during operation]), 05 (DC braking after jogging stops
[enabled during operation])
00
¯ {
4-49
*1 This setting is valid only when the OPE-SR is connected.