Hitachi SJ700-2 Power Supply User Manual


 
Chapter 4 Explanation of Functions
4 - 145
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
003Ah Trip monitoring 5 (factor) See the list of inverter trip factors below -
003Bh Trip monitoring 5 (inverter status) See the list of inverter trip factors below -
003Ch Trip monitoring 5 (frequency) (high)
003Dh Trip monitoring 5 (frequency (low)
0 to 40000 0.01 [Hz]
003Eh Trip monitoring 5 (current) Output current at tripping 0.1 A
003Fh Trip monitoring 5 (voltage) DC input voltage at tripping 1 V
0040h Trip monitoring 5 (running time) (high)
0041h Trip monitoring 5 (running time) (low)
Cumulative running time at tripping 1h
0042h Trip monitoring 5 (power-on time) (high)
0043h Trip monitoring 5 (power-on time) (low)
d085 R
Cumulative power-on time at tripping 1h
0044h Trip monitoring 6 (factor) See the list of inverter trip factors below -
0045h Trip monitoring 6 (inverter status) See the list of inverter trip factors below -
0046h Trip monitoring 6 (frequency) (high)
0047h Trip monitoring 6 (frequency (low)
0 to 40000 0.01 [Hz]
0048h Trip monitoring 6 (current) Output current at tripping 0.1 A
0049h Trip monitoring 6 (voltage) DC input voltage at tripping 1 V
004Ah Trip monitoring 6 (running time) (high)
004Bh Trip monitoring 6 (running time) (low)
Cumulative running time at tripping 1h
004Ch Trip monitoring 6 (power-on time) (high)
004Dh Trip monitoring 6 (power-on time) (low)
d086 R
Cumulative power-on time at tripping 1h
004Eh Programming error monitoring d090 R Warning code -
004Fh to
08FFh
Unused - - Inaccessible -
0900h Writing to EEPROM - W
0000: Motor constant recalculation
0001: Set data storage in EEPROM
Other: Motor constant recalculation and set data
storage in EEPROM
-
0901h to
1000h
Unused - - Inaccessible -
Note 1: Assume that the rated current of the inverter is "1000".
Note 2: If a number not less than "1000" (100.0 seconds) is specified, the second value after the decimal
point will be ignored.