Hitachi SJ700-2 Power Supply User Manual


 
Chapter 5 Error Codes
2) Error indications by protective functions with the digital option board (SJ-DG) mounted
5 - 6
Name Description
Display on digital
operator
Display on
remote operator
ERR1***
SJ-DG error
If timeout occurs during the communication
between the inverter and digital option board, the
inverter will shut off its output and display the error
code shown on the right.
OP1-0
OP2-0
Note: The input mode is determined by a combination of DI switch and rotary switch settings. If the option
board does not operate normally, confirm the DIP switch and rotary switch settings on the option
board.
Functions of the DIP and rotary switches on the digital option board (SJ-DG)
DIP switch
Rotary
switch
Frequency setting
Acceleration/
deceleration time setting
Torque limit
setting
Position
setting
Type Code Data resolution
Switch No.
1 2
Code for
setting
0.01 Hz 0.1 Hz 1 Hz Rate 0.01 sec 0.1 sec 1 sec 1 1 pulse
0
1
2
3
4
5
OFF: PAC
(batch
input
mode)
6
0
1
2
3
4
5
6
7
8
9
A
OFF: BIN
(binary
input)/
ON: BCD
(BCD
input)
ON: DIV
(divided-inp
ut mode)
B
: Input mode specified by switch settings
Note: For details, refer to the instruction manual for the option board.