Chapter 4 Explanation of Functions
4.2.19 DC braking (DB) setting
A051: DC braking enable
A052: DC braking frequency setting
A053: DC braking wait time
A054: DC braking force during deceleration
A055: DC braking time for deceleration
A056: DC braking/edge or level detection for
[DB] input
A057: DC braking force for starting
A058: DC braking time for starting
A059: DC braking carrier frequency setting
C001 to C008: Terminal [1] to [8] functions
Related code
The DC braking function allows you to apply DC braking to the
motor according to the load on the motor.
You can control DC braking in two ways: the external control
through signal input to intelligent input terminals and the internal
control to be performed automatically when the motor is started
and stopped.
Note that the motor cannot be stopped by DC braking if the load
on the motor produces a large moment of inertia.
Item Function code Data or range of data Description
00 Internal DC braking is disabled.
01 Internal DC braking is enabled.
DC braking enable A051
02
Internal DC braking is enabled. (The braking
operates only with the set braking frequency.)
DC braking
frequency setting
A052 0.00 to 60.00 (Hz)
With internal DC braking enabled, DC braking is
started when the output frequency reaches the
set braking frequency.
DC braking wait
time
A053 0.0 to 5.0 (s)
The DC braking wait time specifies the delay in
starting DC braking after the set braking time has
elapsed or the DB terminal has been turned on.
DC braking force
during deceleration/
DC braking force for
starting
A054/A057 0. to 100. (%)
"0" specifies the smallest force (zero current);
"100" specifies the largest force (rated current).
DC braking time for
deceleration
A055 0.0 to 60.0 (s)
This setting is valid for the external DC braking in
edge mode or for the internal DC braking.
00 Edge mode (See examples 1-a to 6-a.) DC braking/edge or
level detection for
[DB] input
A056
01 Level mode (See examples 1-b to 6-b.)
DC braking time for
starting
A058 0.0 to 60.0 (s)
This setting is valid for the internal DC braking.
DC braking is started when the motor-start
command is input.
DC braking carrier
frequency setting
A059 0.5 to 15 (kHz) Unit: kHz
(1) Carrier frequency for DC braking
Use the DC braking carrier frequency setting (A059) to specify the carrier frequency for DC braking. Note
that setting the carrier frequency above 5 kHz automatically lowers the braking force.
See the following graph showing the operation of the DC braking force limiter:
0
80
100
70
60
50
40
30
20
10
90
3 15131195
7
(75)
(46)
(34)
(22)
(10)
DC braking carrier frequency
(kHz)
DC braking force limiter
Maximum braking
force (%)
4 - 20