Juniper Networks EX2200 Switch User Manual


 
If you are mounting an EX2200 switch in a rack or cabinet with other equipment, or if
youareplacingitonthedesktoporfloornearotherequipment,ensurethattheexhaust
from other equipment does not blow into the intake vents of the chassis.
Leave atleast 24in.(61cm) in frontofthe switchand6 in.(15.2 cm) behindthe switch.
For service personnel to remove and install hardware components, you must leave
adequate space at the front and back of the switch. NEBS GR-63 recommends that
you allow at least 30 in. (76.2 cm) in front of the rack or cabinet and 24 in. (61 cm)
behind the rack or cabinet.