Pelco Manual C1515M-A (11/01) 49
Figure 37. Access the Set Auxiliary Screen
MODE: For each auxiliary select the operation mode.
OPTIONS:
ALM = activate the auxiliary as a response to an alarm; if you select
this mode, specify the monitor number and dwell time
LAT = latching operation
MOM = momentary operation
Specify values for the MON and DWL fields only when you select ALM in the MODE field.
MON: Specify the number of the monitor the auxiliary will follow (01-08).
DWL: Specify the amount of time the auxiliary will remain active after there is
no longer an alarm displayed on a monitor (01-99 seconds). The alarm
is displayed on a monitor until
• the alarm is acknowledged manually (if MANUAL is selected in
the alarm contact ACK TYPE field),
• the alarm contact times out (if AUTO is selected in the alarm
contact ACK TYPE field).
Refer to the ACK TYPE description in
Internal and External Alarms
and
in
Video Loss Alarm
.
PELCO SWITCHER
MODEL CM6800
MAIN MENU
1 CAMERA
2 LOGICAL CAMERA
3 MONITOR
4 ACCESS
5 TIME & DATE
6 PORT
7 PRIORITY
8 SEQUENCE
9 MACRO
10 ALARM CONTACTS
11 EVENT TIMER
12 SET AUXILIARY
13 SET PASSWORD
14 ABOUT CM6800
ENGLISH
RETURN
00654
SET AUXILIARY MENU
AUX MODE MON DWL
1 ALM 01 10
2LAT02 43
3 MOM 03 20
RETURN
00643
AUXILIARY OUTPUTS
The three local auxiliary (AUX) outputs on the rear panel of the CM6800 can be operated
manually from a system keyboard or automatically in response to an alarm.
Auxiliary
Programming