90 Installation
Procedure 2
Wall-mounting the WLAN IP Telephony Manager 2245
Step Action
1 Use a 18-inch drill bit to drill four pilot holes, on 1.84 by 12.1 inch
centers (approximately equivalent to 1-1316 inch by 12-18 inch).
2 Insert the #8 x 34-inch screws in the pilot holes and tighten,
leaving a 18 to 14-inch gap from the wall.
3 Slide the WLAN IP Telephony Manager 2245 over the screws
until the WLAN IP Telephony Manager 2245 drops into place in
the keyhole openings of the flange.
4 Tighten screws fully.
--End--
Rack-mount
The rack-mount kit is designed for mounting the WLAN IP Telephony
Manager 2245 in a standard 19-inch rack and contains the following
equipment:
Mounting plates—two for each WLAN IP Telephony Manager 2245 to
be mounted.
Screws—four rack-mount screws for each WLAN IP Telephony
Manager 2245 to be mounted.
Follow the steps in Procedure 3 “Rack-mounting the WLAN IP Telephony
Manager 2245” (page 90) to rack-mount the WLAN IP Telephony Manager
2245.
Procedure 3
Rack-mounting the WLAN IP Telephony Manager 2245
Step Action
1 Remove the corner screws from the WLAN IP Telephony
Manager 2245.
2 Screw the U-shaped end (round screw holes) of the two
mounting plates to the WLAN IP Telephony Manager 2245.
3 Screw the other end of the two mounting plates (oblong screw
holes) to the rack.
4 Repeat steps 1-3 for each additional WLAN IP Telephony
Manager 2245. The mounting plate is designed to provide
Nortel Communication Server 1000
WLAN IP Telephony Installation and Commissioning
NN43001-504 03.04 Standard
23 September 2008