Q-Logic QLA2342 Switch User Manual


 
6 – Removal/Replacement
Fans
6-18 59043-06 A
0
6.5.2
Installing a Power Supply Module
To install a power supply module, do the following:
1. Confirm that the Heartbeat LED is showing the normal 1 blink per second.
This allows the switch to correctly report power supply status.
2. Slide the power supply module into the slot guide until it contacts the
backplane.
3. Rotate the blade latch upward to lock the power supply module in place.
Fasten the screws.
4. Reconnect the power cord to the power supply module and confirm that the
Output Power LED illuminates.
5. Confirm the power supply module status. Do one of the following:
Open a Telnet session and enter the Show Chassis command to
display the operational status of the power supply modules. Refer to
the ”Show Command” on page B-62.
Observe the power supply status in the Switch data window of the
SANsurfer Switch Manager topology display. Refer to the SANbox2-64
Switch Management User’s Guide.
6.6
Fans
The fans are hot pluggable. This means you can remove or install one of the fans
while the switch is operating without disrupting service. The fan is completely
enclosed, so there is no risk of injury from the fan blades. The fans are also
interchangeable; that is, any fan will fit in any bay. Before removing a fan, connect
an ESD wrist strap to a ground point on the chassis or rack.