Installing a DEFINITY ECS ATM-PNC
3-26Synchronization Installation and Testing
3
To install a 400A sync splitter between a CSU or DSU/CSU and a DS1 circuit
pack, follow the procedures listed in Table 3-13
.
Table 3-13. Splitter installation to DS1
Step Action Command Description
1. Disable
synchronization
switch
disable
synchronization
-switch
Prevent the system from switching
synchronization sources.
2. Busyout DS1
circuit pack
busyout board
UUCSS
Busyout the designated DS1 circuit pack.
3. Remove cable
from DS1
circuit pack
Remove the H600-307 cable from the amphenol
connector located on rear of the DS1 circuit
pack.
4. Attach the
splitter
Plug the splitter into the same connector just
vacated by the H600-307 cable.
5. Reconnect the
cable
Plug the H600-307 cable into the connector on
the splitter.
6. Secure the
splitter
Secure the splitter to the carrier using the large
mounting strap removed from a fiber
transceiver.
7. Check
connections
Check that all Amphenol connections are
secure.
8. Release DS1
circuit pack
release board
UUCSS
Restore the designated DS1 circuit pack to
service.
9. Test the splitter Use the procedure in ‘‘Splitter port tests
(401A/401A only)’’ on page 3-19.
Before testing the splitter, insert a modular
RJ45 plug into jack J1 and jack J2.
NOTE:
Do not connect port J1 to port J2. Leave
the other end of both cords free, because
the modular RJ45 plug acts as a opening
plug and removes the 100- termination
from J1 and J2 ports.
After testing is complete, remove the
opening plugs from J1 and J2.
10. Check
DSU/CSU
LEDs
After about 20 s, all the alarm LEDs on the 316X
CSU or DSU/CSU should go out.
If this is the case, perform steps 11 through 12.
Otherwise, go to step 13.
Continued on next page