Baldor VS1MD Computer Drive User Manual


 
7-56 VS1MD AC Drive User Manual
1 = Operation stops when cooling fan malfunctions
When cooling fan fault occurs, message is displayed on the
LED and operation is stopped. If t32 and/or t33 is set to 17 (Fault Output),
fault message is displayed.
H81 -
H90
Second Motor Parameters
Range: See below
Default: See below
Access Configurable
See Also: t1-t8
These parameters activate when a selected terminal is ON and one of the
t1 thru t8 terminals is set for 12 (2
nd
Motor Select).
Use these settings when an inverter operates two motors connected to two
different types of loads. 2
nd
motor operation does not drive two motors at
the same time. When first selected motor operation is stopped, select a
terminal for the second motor and define H81 thru H90 to run the second
motor.
Sets the V/F pattern for the second motor.
Param. Description Range Factory Default Adj. run
H81 Accel Time 0 ~ 60000 Sec 1.0
H82 Decel Time 0 ~ 60000 Sec 5.0
H83 Base Freq 30 ~ 400 Hz 60.0 -
H84 V/F Pattern 0 ~ 2 0 -
H85 FX Torque Boost 0 ~ 15 % 5 -
H86 RX Torque Boost 0 ~ 15 % 5 -
H87 Stall Level 30 ~ 150 % 150 -
H88 1 Min Overload Level 50 ~ 200 % 150
H89 Continuous Overload Level 50 ~ 150 % 100
H90 Motor Rated Current 0.1 ~ 50 Amps 26.3 -
M 1
M 2
VS1MD
P8