Baldor VS1MD Computer Drive User Manual


 
Parameter Descriptions 7-11
P43 Preset Speed 1
P44 Preset Speed 2
P45 Preset Speed 3
Range: 0 - 400 [Hz]
Default:
P43 = 10, P44 = 20, P45 = 30
Access Tunable
See Also:
t1-t8, t10-t13
Provides an internal fixed speed command selectable by digital inputs.
P46 Drive Start/Stop Source 2
Range: 0 - 3 (see table for P38)
Default: 1 = Terminal Mode 1
Access Configurable
See Also:
P38, t1-t8
Note: Only viewable when one of the t1-t8 terminals is set
for 22 and P38 = 3 (RS485 Communications).
When RS485 communications is used as the primary mode of controlling
the drive, this parameter serves as an alternate mode. It is selectable by a
digital input (t1-t8) = “22”.
P47 Frequency Setting Mode 2
Range: 1-7 (see table for P40)
Default:
1 = Keypad
Access Configurable
See Also:
P40, P47, t1-t8
Note: Only viewable when one of the t1-t8 terminals is set
for 22 and P40 = 7 (RS485 Communications).
When RS485 communications is used as the primary mode of controlling
the drive, this parameter serves as an alternate mode. It is selectable by a
digital input (t1-t8) = “22”.