Baldor VS1MD Computer Drive User Manual


 
7-28 VS1MD AC Drive User Manual
7.5 Function Group 1 Parameters
F0 Jump Code
Range: 0-64
Default: 0
Access Tunable
Sets the code to jump directly to a specific parameter within the group.
F1 Forward/Reverse Run Disable
Range: 0 = Forward and Reverse run enable
1 = Forward run disable
2 = Reverse run disable
Default: 0
Access Configurable
Enables/disables the function that allows the direction of the motor rotation
to be changed. The forward or reverse command may come from a digital
command, the keypad or serial command. All forward or reverse inputs will
be ignored if the corresponding directional control is disabled in F1.
F2 Accel Pattern
F3 Decel Pattern
Range: 0=Linear
1=S-Curve
Default: 0
Access Configurable
See Also: H17, H18, t1-t8
Sets the acceleration and deceleration pattern in the drive.
Linear: General pattern for constant torque applications.
S-Curve:This curve allows the motor to accelerate and decelerate smoothly.
To adjust the slope of the S-Curve see parameters H17 and H18.