Baldor VS1MD Computer Drive User Manual


 
7-48 VS1MD AC Drive User Manual
H37 Load Inertia Rate
Range: 0=Load inertia rate is less than 10 times that of motor
inertia
1=Load inertia rate equal to approximately 10 times the
motor inertia.
2=Load inertia rate is more than 10 times that of motor
inertia.
Default: 0
Access Configurable
See also: F8-F11, H40
Select range according to the connected inertia in relationship to the motor
inertia.
H39 Carrier Frequency Select
Range: 2-15 [kHz]
Default: 2
Access Tunable
This parameter affects the audible sound of the motor, noise emission form
the inverter, inverter temperature, and leakage current. If the set value is
higher, the inverter sound is more quiet, but the noise from the inverter and
leakage current will be increased.
H40 Control Mode Select
Range: 0=Volts/Frequency Control
1=Slip Compensation Control
2=PID Feedback Control
3=Sensorless Vector Control
Default: 0
Access Configurable
This parameter selects the control mode for the operation of the drive. See
the following description of control method and the corresponding
parameters for adjustment to each.