Baldor VS1MD Computer Drive User Manual


 
Troubleshooting 9-9
9.7 Overload Protection
IOLT : IOLT(inverter Overload Trip) protection is activated at 150% of the inverter
rated current for 1 minute and greater.
OLT : OLT is selected when F56 is set to 1 and activated at 200% of F57[Motor rated
current] for 60 sec in F58. This can be programmable.
Electronic
Thermal
Motor has
overheated.
Reduce load and/or
duty cycle.
Load is greater than
inverter rating.
Change drive with
higher capacity.
ETH level is set too
low.
Adjust ETH level to an
appropriate level.
Drive capacity is
incorrectly selected.
Select correct drive
capacity.
External fault A
contact input
The terminal set to “18
(External fault-A)” or
“19 (External fault-B)”
in t1-t8 within terminal.
Eliminate the cause of
fault in the circuit
connected to external
fault terminal.
External fault B
contact input
Operating
method when
the frequency
command is
lost
No frequency
command is applied to
V1 and I.
Check the wiring of V1
and I and frequency
reference level.
Remote
keypad
communication
error
Communication error
between drive keypad
and remote keypad.
Check for connection
of communication line
and connector.
EEP: Parameter save error
HWT: Hardware fault
Err: Communication error
COM: Keypad error
NTC: NTC error
Call Baldor-Reliance
for assistance.
Table 9.2 – Corrective Actions