Baldor VS1MD Computer Drive User Manual


 
4-6 VS1MD AC Drive User Manual
4.5 Recommended Breakers
4.6 Recommended Fuses and AC Reactors
Table 4.3 – Circuit Breaker Ratings by Model Number
Model Breaker Model Breaker
Current[A] Voltage[V] Current[A] Voltage[V]
VS1MD20P5
30 230
VS1MD40P5 30 460
VS1MD21 30 230
VS1MD41 30 460
VS1MD22 30 230
VS1MD42 30 460
VS1MD23 30 230
VS1MD43 30 460
VS1MD25 30 230
VS1MD45 30 460
VS1MD27 50 230
VS1MD47 30 460
VS1MD10 60 230
VS1MD410 30 460
Model External fuse AC reactor
Current[A] Voltage[V]
VS1MD20P5
10 A 500 4.20mH, 3.5A
VS1MD21 10 A 500 2.13mH, 5.7A
VS1MD22 15 A 500 1.20mH, 10A
VS1MD23 25 A 500 0.88mH,14A
VS1MD25 40 A 500 0.56mH, 20A
VS1MD27 40 A 500 0.39mH, 30A
VS1MD210 50 A 500 0.28mH, 40A
VS1MD40P5 5 A 500 18.0mH, 1.3A
VS1MD41 10 A 500 8.63mH, 2.8A
VS1MD42 10 A 500 4.81mH, 4.8A
VS1MD43 10 A 500 3.23mH, 7.5A
VS1MD45 20 A 500 2.34mH, 10A
VS1MD47 20 A 500 1.22mH, 15A
VS1MD4100 30 A 500 1.14mH, 20A
!
ATTENTION:Suitable For Use On A Circuit Capable Of Delivering
Not More Then 65,000 RMS Symmetrical Amperes. 240V drives
or 480V drives Volts Maximum
ATTENTION:Use Class H or K5 UL Listed Input Fuse and UL
Listed Breaker Only. See the table above for the voltage and current
rating of the fuse and the breaker.