Baldor VS1MD Computer Drive User Manual


 
7-42 VS1MD AC Drive User Manual
H10 Skip Frequency Enable
Range: 0 - 1
Default: 0
Access Configurable
See also: H11-H16
Set this parameter = 1 to enable the skip frequency settings configured in
H11 thru H16. When it is desirable to avoid resonance attributable to the
natural frequency of a mechanical system, these parameters allow resonant
frequencies to be skipped. Three different areas of Skip frequency
High/Low limit can be set. During acceleration or deceleration however, the
run frequency within the set area is valid.
H11 Skip Frequency Low Limit 1
H12 Skip Frequency High Limit 1
H13 Skip Frequency Low Limit 2
H14 Skip Frequency High Limit 2
H15 Skip Frequency Low Limit 3
H16 Skip Frequency High Limit 3
Range: 0.1-400 [Hz]
Default: H11=10, H12=15, H13=20, H14=25, H15=30, H16=35
Access Configurable
See Also: H10
Note: Parameters H11-H16 are only viewable when H10 – Skip
Frequency = 1 (Enabled).
Run frequency cannot be set within the range of H11 thru H16. The
frequency values of the low numbered parameters cannot be set above
those of the high numbered ones. Settable within the range of Frequency
High and Low Limits (P35 and P36).Sets the lower limit of frequency range
1 to skip.
Run
command
Freq.
H11
H12
H13
H14
H15
H16
V1(Voltage input)
0
20mA
10V
I (Current input)
Freq. Up setting
Freq. Down
setting