Baldor VS1MD Computer Drive User Manual


 
7-6 VS1MD AC Drive User Manual
The drive outputs its rated voltage to the motor at this frequency (enter motor
nameplate). See parameter F30 for custom V/Hz settings and V/Hz curve.
Sets drive minimum steady state output frequency.
Sets drive maximum steady state output frequency.
This parameter manually sets the frequency that the drive is commanded to output.
Set the desired frequency and press ENTER/PROG to lock the value into memory. If
the drive is running, it will immediately accelerate or decelerate to this value once
enter is pressed. If the drive is not running, entering a value in P37 will pre-set the
speed to accelerate to after a valid run command.
P34 Base Frequency
Range: 30 - 400 [Hz]
Default:
60
Access Configurable
See Also:
P30, P33, F30-F38
P35 Frequency Low Limit
Range: 0 - P36 [Hz]
Default:
10.0
Access Configurable
See Also:
P36, F30-F38
P36 Frequency High Limit
Range: 0 - 400 [Hz]
Default:
60.0
Access Configurable
See Also:
P35
P37 Frequency Command
Range: 0 - 400 [Hz]
Default:
0.00
Access Tunable