Baldor VS1MD Computer Drive User Manual


 
7-34 VS1MD AC Drive User Manual
F39 Output voltage adjustment
Range: 40-110 [%]
Default: 100
Access Configurable
This parameter adjusts the amount of output voltage, set as a percentage of
input voltage. Use when the motor voltage is less than the input voltage.
F40 Energy Savings Level
Range: 0-30 [%]
Default: 0
Access Tunable
This parameter adjusts decreases the output voltage according to load
status. It is set as a percent of the maximum output voltage. When used on
pump and fan applications, it can dramatically reduce energy consumption
by decreasing the output voltage with light loads.
F50 Electronic thermal select
Range: 0 - 1
Default: 0
Access Tunable
Read Only: F51-F53
Setting this parameter to a 1 enables the electronic thermal overload. It
activates when the motor is overheated if current is greater than the value
set in F51 (time-inverse), and the drive output is turned off for the preset
time.
Only viewable when F50 = 1 (Electronic Thermal Overload).