Baldor VS1MD Computer Drive User Manual


 
Parameter Descriptions 7-31
F14 Time for magnetizing a motor
Range: 0-60 [sec]
Default: 0.1
Access Configurable
See Also: P30, P32, H32, H34, H40, H42, H44
This parameter accelerates the motor after pre-exciting the motor for the set
time. The amount of the pre-exciting current is set in H34 – Motor no load
current.
F20 Jog Frequency
Range: 0-400 [Hz]
Default: 10.00
Access Tunable
See Also: P36, t1-t8
This parameter sets the Jog Frequency, it cannot be set above P36 –
Frequency High Limit. Jog is only available in 2-wire control mode.
F27 Torque Boost select
Range: 0=Manual Torque Boost
1=Auto Torque Boost
Default: 0
Access Configurable
See Also: F28-F29, H34, H41-42
If F27 = 0, set manual torque boost values in F28 and F29.
If F27 = 1 (Auto toque boost), the inverter automatically calculates torque
boost values using motor parameters and outputs the corresponding
voltage. Before enabling Auto torque boost, H34 – No load current and H42
– Stator resistance must be set properly.
FX
Time
RX
Voltage
F28 - FX
torque boost
No torque boost
100%
F29 - RX
torque boost