Baldor VS1MD Computer Drive User Manual


 
9-8 VS1-MD AC Drive User Manual
Inverter
overheat
Cooling system has
problems.
Check for foreign
substances clogged in
the heat sink.
Cooling fan has failed. Replace the old
cooling fan with a new
one.
Ambient temperature
is too high.
Keep ambient
temperature under 50
degrees C.
Output Phase
loss
Faulty contact in
output contactor.
Replace or repair
output contactor.
Faulty output wiring Check output wiring.
Cooling Fan
Fault
An foreign substance
is clogged in a
ventilating slot.
Check the ventilating
slot and remove the
clogged substances.
Cooling fan has failed. Replace the cooling
fan.
Over voltage
Decel time is too short
for the inertia of the
load.
Increase the Decel
time.
Regenerative load is
connected to the
drive.
Use Dynamic Brake
Unit.
Line voltage is too
high.
Check to see if line
voltage exceeds the
rating.
Low voltage
Line voltage is low. Check to see if line
voltage is below the
rating.
Load larger than line
capacity is connected
to line (ex: welding
machine, motor with
high starting current
connected to the
commercial line).
Check the incoming
AC line. Adjust the
line capacity
corresponding to the
load.
Faulty contactor on
the input of the
inverter.
Change contactor.
Table 9.2 – Corrective Actions