Options & Kits B-3
Step 3. Attach the top cover of the I/O board kit and connect the remote cable as
shown below.
Step 4. Connect the other side of the remote cable to the remote keypad as shown
below.
!
!
WARNING: Do not touch any circuit board, power device or electrical
connection before you first ensure that power has been disconnected and
there is no high voltage present from this equipment or other equipment to
which it is connected. Electrical shock can cause serious or fatal injury.
Only qualified personnel should attempt the start-up procedure or
troubleshoot this equipment.
!
!
WARNING: Do not remove cover for at least ten (10) minutes after AC
power is disconnected to allow capacitors to discharge. Dangerous
voltages are present inside the equipment. Electrical shock can cause
serious or fatal injury.
!
!
ATTENTION:Without Parameter Read (H91), Parameter Write (H92) is
not available since the Remote memory is empty when the Remote
keypad is first used.
ATTENTION:Use only the remote cable supplied in the kit. Other cables
may introduce noise and/or voltage drop and cause erratic or improper
drive operation.
ATTENTION:Check for disconnection of the communication cable
and/or poor cable connection if ì----ì is displayed on the 7-segment
display of the Remote keypad.