Baldor VS1MD Computer Drive User Manual


 
7-20 VS1MD AC Drive User Manual
t30 Frequency detection level
t31 Frequency detection bandwidth
Range: 0-400 [Hz]
Default: t30 = 30, t31 = 10
Access Tunable
See also: t32-t33
Used when t32 or t33 are set to 0-4, can not be set higher than P36
(Frequency High Limit). See Chapter 8 - Customizing Your Application for
more information.
t32 Digital Output (MO)
t33 Relay Output ( 3A - 3C)
Range: 0 = FDT-1
1 = FDT-2
2 = FDT-3
3 = FDT-4
4 = FDT-5
5 = Overload (OLt)
6 = Inverter Overload (LoIT)
7 = Motor Stall STALL
8 = Over voltage trip (OV)
9 = Low voltage trip (LV)
10 = Inverter overheat (OH)
11 = Command Loss
12 = During run
13 = During stop
14 = During constant run
15 = During speed searching
16 = Wait time for run signal input
17 = Fault Output
18 = Cooling Fan Trip Alarm
Default: t32=12, t33=17
Access Tunable
See Also: t34, F54-F55, F59-F60
Sets the on/off point for the Digital and Relay outputs. See Chapter 8 –
Customizing Your Application for details on this parameter.
t34 Fault Relay Output
Range: 0-7
Default: 2
Access Tunable
See Also: t33
Outputs a fault code when t33 – Relay Output is set to 17: Fault Output.
See Chapter 8 – Customizing Your Application for more information on this
parameter.