Baldor VS1MD Computer Drive User Manual


 
6-10 VS1MD AC Drive User Manual
6.9 Monitoring Display Parameters
The Display group is a group that consists of read only values that can be monitored
by the user to diagnose the operation of the drive and motor. To monitor the motor
current, follow the below example.
Step 9. Press the ENTER key to accept the value and the
display will begin to flash so that you can confirm the
entry.
Step 10. Press the ENTER key a second time to acknowledge
the entry. The display will revert to showing the
parameter number.
Table 6.8 – Modifying Parameter Values
Table 6.9 – Monitoring Display Parameters
Step 1. From the operation mode, press and hold down the
ENTER key for at least 2 seconds to change the
drive to the programming mode. The “PROG” LED
will illuminate indicating that you are in the
programming mode. The drive will display the first
parameter of the “Display” group.
Step 2. Press the up arrow key twice to change to the
parameter d2 (Motor Current).
Step 3. Momentarily press the ENTER key to display the
motor current. The display will be updated in real
time.
Step 4. Press the ENTER key to return to the previous
display so that you can select a new parameter to
view.
Display Group