Baldor VS1MD Computer Drive User Manual


 
7-24 VS1MD AC Drive User Manual
t47 Frequency corresponding to t46
Range: 0 - 400 [Hz]
Default: 0
Access Tunable
See Also: t46
Sets the inverter output minimum frequency at minimum current of the I
input.
t48 Analog Input 0-20mA (I) Max Current
Range: 4 - 20mA
Default: 20
Access Tunable
See Also: t47
Sets the maximum current of the Analog 0-20mA (I) Input.
t49 Frequency corresponding to t47
Range: 0 - 400 [Hz]
Default: 60
Access Tunable
See Also: t48
Sets the inverter output maximum frequency at maximum current of the I
input.
t57 Keypad Error Output
Range: 0 - 3
Default: 0
Access Tunable
Selects the Digital and/or Relay output when a keypad-inverter
communication fails.
When communication error occurs for a certain time, will be
displayed and the error signal can be sent to the Digital (MO) or Relay
output.
Relay Output
Bit 2
Digital Output
Bit 0
0-
1-
2
3
-
-
0: Not used 1: Signal output to MO
2: Signal output to 3A, 3B contacts 3: Signal output to MO, 3A, 3B